Flair Shunt Capacitor Design Features
Dielectric: Metalized film
Filling Material: Heat convertible resin
Safety Protection Device: Each element is mounted with a safety protection device to prevent explosion or short-circuit failures, ensuring failed elements separate cleanly from the circuit.
Built-in Discharge Resistor: Available for rapid voltage reduction.
Package: Stainless steel shell, hermetically sealed
Frequency: 50Hz
Shell Construction: 1mm galvanized stainless steel shell with superior heat dissipation effect
Thermal Optimization: Sufficient space between elements to lower internal temperature and boost heat dissipation
Internal Fuse: Integrated protection available
Internal Busbar: Pure copper busbar connection (low current density, low contact resistance, low loss)
Discharge Performance: Fixed connection discharge resistor (decreases voltage below 75V within 3 minutes after power cut-off, upon request)
Environment Temperature: -20°C ~ +50°C
Operational Altitude: Below 2000m
Specification Table
| Model | Capacity | Current | Capacitance | Weight | Dimension (mm) | ||
|---|---|---|---|---|---|---|---|
| kvar | A | μF | kg | Length | Width | Height | |
| 3-Phase 400VAC 50Hz Indoor | |||||||
| FACS-BC3 | 25 | 20.8×3 | 166×3 | 5.0 | 200~240 | 112 | 242 |
| FACS-BC3 | 30 | 25.0×3 | 199×3 | 5.0 | 200~240 | 112 | 242 |
| FACS-BC3 | 40 | 33.3×3 | 265×3 | 6.5 | 200~240 | 112 | 306 |
| FACS-BC3 | 50 | 41.7×3 | 332×3 | 7.8 | 200~240 | 112 | 370 |
| FACS-BC3 | 60 | 50.0×3 | 398×3 | 9.0 | 200~240 | 112 | 435 |
| 3-Phase 460VAC 50Hz Indoor | |||||||
| FACS-BC3 | 20 | 14.5×3 | 100×3 | 4.2 | 200~240 | 112 | 178 |
| FACS-BC3 | 25 | 18.1×3 | 125×3 | 5.0 | 200~240 | 112 | 242 |
| FACS-BC3 | 30 | 21.7×3 | 150×3 | 5.0 | 200~240 | 112 | 242 |
| FACS-BC3 | 40 | 29.0×3 | 201×3 | 6.5 | 200~240 | 112 | 306 |
| FACS-BC3 | 50 | 36.2×3 | 251×3 | 7.8 | 200~240 | 112 | 370 |
| FACS-BC3 | 60 | 43.5×3 | 301×3 | 9.0 | 200~240 | 112 | 435 |
| Application Note: The capacitor internal is not connected; generally used for capacitor triangle connection angle in the fling-cut switch. | |||||||
| Model | Capacity | Current | Capacitance | Weight | Dimension (mm) | ||
|---|---|---|---|---|---|---|---|
| kvar | A | μF | kg | Length | Width | Height | |
| 3-Phase 400VAC 50Hz | |||||||
| FACS-BC3Y | 6 | 8.7 | 119 | 3.6 | 200~240 | 112 | 114 |
| FACS-BC3Y | 12 | 17.3 | 239 | 4.3 | 200~240 | 112 | 178 |
| FACS-BC3Y | 18 | 26.0 | 358 | 5.1 | 200~240 | 112 | 242 |
| FACS-BC3Y | 24 | 34.6 | 477 | 6.5 | 200~240 | 112 | 306 |
| FACS-BC3Y | 30 | 43.3 | 597 | 7.8 | 200~240 | 112 | 370 |
| FACS-BC3Y | 36 | 52.0 | 716 | 9.1 | 200~240 | 112 | 435 |
| 3-Phase 440VAC 50Hz | |||||||
| FACS-BC3Y | 7 | 9.2 | 115 | 3.6 | 200~240 | 112 | 114 |
| FACS-BC3Y | 14 | 18.4 | 230 | 4.3 | 200~240 | 112 | 178 |
| FACS-BC3Y | 21 | 27.6 | 345 | 5.1 | 200~240 | 112 | 242 |
| FACS-BC3Y | 29 | 38.1 | 477 | 6.5 | 200~240 | 112 | 306 |
| FACS-BC3Y | 36 | 47.2 | 592 | 7.8 | 200~240 | 112 | 370 |
| FACS-BC3Y | 43 | 56.4 | 707 | 9.1 | 200~240 | 112 | 435 |
| Application Note: The capacitor internal is wye (star) connection. | |||||||
| Model | Capacity | Current | Capacitance | Weight | Dimension (mm) | ||
|---|---|---|---|---|---|---|---|
| kvar | A | μF | kg | Length | Width | Height | |
| 3-Phase 400VAC 50Hz Indoor | |||||||
| FACS-BC | 20 | 28.9 | 398 | 4.2 | 200~240 | 112 | 178 |
| FACS-BC | 25 | 36.1 | 497 | 5.0 | 200~240 | 112 | 242 |
| FACS-BC | 30 | 43.3 | 597 | 5.0 | 200~240 | 112 | 242 |
| FACS-BC | 40 | 57.7 | 796 | 6.5 | 200~240 | 112 | 306 |
| FACS-BC | 50 | 72.2 | 995 | 7.8 | 200~240 | 112 | 370 |
| FACS-BC | 60 | 86.6 | 1194 | 9.0 | 200~240 | 112 | 435 |
| 3-Phase 460VAC 50Hz Indoor | |||||||
| FACS-BC | 20 | 25.1 | 301 | 4.2 | 200~240 | 112 | 178 |
| FACS-BC | 25 | 31.4 | 376 | 5.0 | 200~240 | 112 | 242 |
| FACS-BC | 30 | 37.7 | 451 | 5.0 | 200~240 | 112 | 242 |
| FACS-BC | 40 | 50.2 | 602 | 6.5 | 200~240 | 112 | 306 |
| FACS-BC | 50 | 62.8 | 752 | 7.8 | 200~240 | 112 | 370 |
| FACS-BC | 60 | 73.3 | 903 | 9.0 | 200~240 | 112 | 435 |
| Application Note: The harmonic filtering capacitor is usually connected with a reactor in series to filter harmonic frequencies in the power system. | |||||||